  • Sensing input voltage: 190 -264V ac max,2 or 3 phase
  • Power input (PMG) Voltage: 190-220V ac max.3 phase ,3 wire
  • Power input (PMG) current: 3A/phase
  • AVR MX321 Automatic Voltage Regulator For Generator Alternator Genset Volt Regulation



Product Description

FDJ03
32103
SAME AVR AS:
  • AVR E000-23212/1P VOLTAGE REGULATOR
  • AVR E000-23210 VOLTAGE REGULATOR
  • AVR 305-0823 VOLTAGE REGULATOR
  • AVR 594-010 VOLTAGE REGULATOR
  • AVR 594-158 VOLTAGE REGULATOR
  • AVR 44R4421811 VOLTAGE REGULATOR
Output

Voltage:

Max 120V dc

Current:

Continuous 3.7 A ( see note 1 )

Intermittent 6A for 10 secs

resistance:

15 ohms minimum

regulation:

+/- 0.5% RMS with 4% engine governing (see note 2 )

Thermal drift:

0.02% per deg .C change in AVR ambient (note 3 )

Soft start ramp time:

0.4 – 4 seconds

Technical specification

Sensing input

voltage:

190 -264V ac max,2 or 3 phase

Frequency:

50-60 Hz nominal

Power input (PMG)

Voltage:

190-220V ac max.3 phase ,3 wire

current:

3A/phase

32101

Typical system response

AVR response:

10 ms

Filed current to 90%:

80 ms

Machine volts to 97%:

300 ms

External voltage adjustment:

+/- 10% with 5 k ohm 1 watt trimmer (see note 4 )

32102

Under frequency protection

Set point:

95% Hz (see note 5 )

Slope:

100-300% down to 30 Hz

Max Dwell:

20% volts/s recovery

Unit power dissipation:

18 watts maximum

32104

Analogue input

Maximum input:

+/- 5V dc (see note 6)

sensitivity:

1v for 5% generator volts (adjustment )

Input resistance:

1k ohm

32105

Quadrature input

10 ohms burden

Max sensitivity:

0.22 A for 5% droop OPF

Max input:

0.33 A

32106

Current voltage detection input

Set point:

300V .time delay:1 sec(fixed )

CB trip coil volts:

10 – 30 V dc

CB trip coil resistance:

20-60 ohms

32107

Over excitation protection

Set point:

75 V dc

Time delay:

8-15 seconds( fixed )

32107

environmental

vibration:

20 – 100 Hz 50mm/sec

100Hz – 2k Hz 3.3g

Operating temperature:

-40 to +70 degree

Relative humdity 0-70 degree:

95% (see note 7 )

Storage temperature:

-55 to + 80 degree

Notes:

1.Derate linearly from 3.7A at 50 degree to 2.7A at 70 degree.

2.The stated voltage regulation may not be maintained in the presure of certain transmitted radio signals, Any change in regulation will fail within the limits in criteria B of BS.EN.61000-6-2:2001